Perle Systems CSS Network Card User Manual


 
Modbus Commands
34 IOLAN SDS/SCS/STS CLI Reference Guide, Version 3.6
Show Modbus
req-next-delay
A delay, in milliseconds, to allow serial slave(s) to re-enable receivers before issuing
next Modbus Master request. The default is 50 ms.
exceptions
When enabled, an exception message is generated and sent to the initiating Modbus
device when any of the following conditions are encountered: there is an invalid UID,
the UID is not configured in the Gateway, there is no free network connection, there is
an invalid message, or the target device is not answering the connection attempt. The
default is On.
idle-timer
Specifies the number of seconds that must elapse without any network or serial traffic
before a connection is dropped. If this parameter is set to 0 (zero), a connection will not
be dropped (with the following exceptions: the TCP KeepAlive causes the connection
to be dropped or the Modbus device drops the connection). The default is 10 seconds.
mess-timeout
Time to wait, in milliseconds, for a response message from a Modbus TCP or serial
slave (depending if the Modbus Gateway is a Master Gateway or Slave Gateway,
respectively) before sending a Modbus exception. The default is 1000 ms.
port
The network port number that the Slave Gateway will listen on for both TCP and UDP
messages. The default is 502.
req-queuing
When enabled, allows multiple, simultaneous messages to be queued and processed in
order of reception. The default is
On.
remapped-id
Specify the UID that will be inserted into the message header for the Slave Modbus
serial device. Valid values are 1-247.
ssl
When enabled, messages over the TCP connection are encrypted vis SSL/TLS.
Description Displays the Modbus Gateway parameters.
User Level Admin
Syntax
show modbus gateway
show modbus slave|master <line_number>