PB
CPP Monitor 2000 User’s Manual
0C Clear Max Min for 3
0D Clear Max Min for 4
0E Clear Max Min for 5
0F Clear Max Min for 6
10 Clear Max Min for 7
11 Clear Max Min for 8
12 Clear Max Min for 9
13 Clear Max Min for 10
Function 11 - Report Slave Identification
Byte/Description
00 Echo of slave address
01 Function - 11
02 Byte count
03 Slave ID - 0x6F for CPP product
04 Run indicator status - 0x00=OFF, 0xFF=ON
05 Unit type ID - 0x01 for CPP Monitor 2000
06 Access Level 0=None 1=Read Only (Status) 2=Read/Write
(Programming)
Input Types:
The following is the list of available input types that can be selected
at offset 10h of the input programming.
* 0: Normally Open
* 1: Normally Closed
* 2: 2.8k Thermistor reading Fahrenheit
* 3: 2.8k Thermistor reading Celsius
* 4: 10k Thermistor reading Fahrenheit
* 5: 10k Thermistor reading Celsius