Powerware 9315 Power Supply User Manual


 
20
Powerware 9315 (200 kVA---300 kVA) Operation
164201036 Rev. D 041500
Using the LCD Screen
The L CD screen at the top of the Monitor Panel provides an o perator interface with
the UPS. Figure 9 identifies the display fields discussed in the following sections.
Uninterruptible Power System
System Normal
Alarm: None
Notice: None
Meters
System
Load Amps
Events Statistics Graphics Setup
Input Output
Bypass Battery
VAB
480
VBC VCA
KW
379
KVA
399
IA IB IC
FREQ
60.0
PF
0.95
V
540
I
000
Meters
480
480 480
480480
VAB
480
VBC VCA
480 480
IA IB IC
361 361361
IN
000
VAB
480
VBC VCA
480 480
FREQ
60.0
KVA
300
KW
240
PF
0.80
Battery
04 MAY 1997 14:23:45
100%
Percent
A
E
D
C
B
F
G
Figure 9. Parts of the LCD Screen (Typical for Powerware 9315 300 480/480V Unit)
A The UPS status area contains three lines that display the current state of t he UPS. The first
line shows the present operational mode of the UPS. The second line shows the highest level
of the current active alarms, and the third line shows a ny notices t he UPS has posted. (For
more information about alarms and notices, refer to Chapter 11, “Responding to System
Events.”)
B The battery charge box shows the percentage of battery capacity available.
C The menu box shows the currently selected menu and lists the options available on that
menu. The title at the top of the menu box is also shown below on the menu bar (E). Press
the
and pushbuttons to scroll up and down through the options in the menu box.
D The currently selected option is highlighted in the menu box. Press the and pushbuttons
to move the highlight up or down. The data in the information area (G) changes accordingly.
E The menu bar lists the titles of the menus. The title of the menu currently displayed in the
menu box is highlighted. When you press the
and pushbuttons to move the highlight
left or right, the data in the menu box a nd the information area change accordingly.
F The timestamp shows the current date and t ime. This date and time are recorded in the Event
Log when a notice or alarm is activated.