Powerware 9315 Power Supply User Manual


 
76
Powerware 9315 (200 kVA---300 kVA) Operation
164201036 Rev. D 041500
System Output
Rectifier/Charger Capacity 125%
DC Filtering Ripple voltage less than 0.5% peak to peak
UPS Output Capacity 100% rated current at 0.8 power factor
Output Voltage Regulation 1% (10% to 100% load)
Output Voltage Adjustment
(Nominal +/--5%)
208 VAC nominal, adjustable from 198 VAC
to 218 VAC (60 Hz only)
480 VAC nominal, adjustable from 456 VAC
to 504 VAC (60 Hz only)
600 VAC nominal, adjustable from 570 VAC
to 630 VAC (60 Hz only)
400 VAC nominal, adjustable from 380 VAC
to 420 VAC (50/60 Hz)
Output Voltage Harmonic Content 3% max THD, 2% max single (for linear load)
Output Voltage Balance 3% for 100% maximum load imbalance
Output Voltage Phase
Displacement
3˚ for 100% maximum load imbalance
Output Transients 5% for 100% load step or removal
Frequency Regulation 0.01 Hz free running
Synchronous to Bypass Bypass within voltage limits of +5%, ---8% of
output setting; bypass within 0.5 Hz
Frequency Slew Rate 1 Hz per second ma ximum (adjustable)
Overload Capability 1125% for 10 minutes
1150% for 10 seconds
Maximum Output Capability 300% peak for 10 cycles without bypass