Environmental Specifications
Operating Temperature 0to40˚C without derating. However, operating
at or near 40˚C will advers ely affect battery life
(refer to your battery specifications for more
information). The recommended operating
temperature is 25˚C.
Operating Altitude Maximum 1500m (5000 ft) at 40_C without
derating
Storage Temperature --- 2 0 t o + 70 ˚C (prolonged storage above 40˚C
will cause rapid battery self-discharge)
Relative Humidity (operating and
storage)
95% maximum noncondensing
Acoustical Noise 65 dBA at a 1m distance
EMI Supression Meets FCC Regulation 47, Part 15, Subpart J, for
class A devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801---2 specifications. Withstan ds up
to 25 kV w ithout damage and with no disturbance
or adverse effect to the critical load.
System Efficiency a t Full Unity
PowerFactorLoadandNominal
Input Voltage
Note: The 208/600 systems use an
input isolation transformer
option that reduces system
efficiency.
400V, 600V Models:
91%
480V Models
:
92%
.
Battery Specifications
These specifications are for batteries supplied by the UPS manufacturer in
line-up-and-match cabinets:
Battery Type Sealed, maintenance-free, high rate discharge, lead-acid
cells
Nominal Battery Stri ng
Voltage
480 VDC (240 cells) for Pow erware
Plus 225, 300
420 VDC (210 cells) for
Powerware
Plus 200, 250
Float Charging 2.25 VDC per cell
(540 VDC based on 240 cells)
(470 VDC based on 210 cells)
Equalizing Charge 2.40 VDC per cell, set to 2.25 VDC at factory
Battery Charge Current
Limit
Limited to 25% of full, regardless of actual load on inverter