Powerware 9315 Power Supply User Manual


 
23
Powerware 9315 (200 kVA---300 kVA) Operation
164201036 Rev. D 041500
Using the Menu Options
The UPS menus allow you to display data in the information area to help you
monitor and control UPS operation. The following m enus and options are
available:
· Meters Displays UPS performance meters for the system or critical load.
· Events Displays the list of Active System Events and a historical log of
system events.
· Statistics Displays statistical information about UPS operations for the
battery, load, or line.
· Graphics Displays a real-time graphic representation of the flow of current
through the internal UPS components.
· Setup Allows you to configure the UPS communications port and set
the date and time for the timestamp.
Figure 10 shows the LCD screen as it appears when you first start the UPS. The Meters
menu is displayed in the menu box, w ith the System option highlighted. In the
information area, the system meters show their current readings.
Uninterruptible Power System
System Normal
Alarm: None
Notice: None
Meters
System
Load Amps
Events Statistics Graphics Setup
Input Output
Bypass Battery
VAB
480
VBC VCA
KW
379
KVA
399
IA IB IC
FREQ
60.0
PF
0.95
V
540
I
000
Meters
480
480 480
480480
VAB
480
VBC VCA
480 480
IA IB IC
361 361361
IN
000
VAB
480
VBC VCA
480 480
FREQ
60.0
KVA
300
KW
240
PF
0.80
Battery
04 MAY 1997 14:23:45
100%
Percent
Figure 10. System Meters Screen (Typical for Powerware 9315 300 480/480V Unit)
The Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the KVA, KW, and power factor measurements. The output
area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery
area displays the DC voltage (V) and the DC current (I).