RuggedCom RS910L Switch User Manual


 
23
2007 RuggedCom Inc. All rights reserved Rev100
5 Technical Specifications
5.1 Operating Environment
Parameter Range Comments
Ambient Operating Temperature
-40 to 85°C
Ambient Temperature as
measured from a 30 cm radius
surrounding the center of the
RS910 enclosure.
Ambient Storage Temperature
-40 to 85°C
Ambient Relative Humidity 5% to 95% Non-condensing
Table 6 - Operating Environment
5.2 Power Supply Specifications
Power Supply Type
Minimum
Input
Maximum
Input
Fuse
Rating
Isolation
Maximum Power
Consumption
12 – 24 VDC 10 VDC 36 VDC 3.15 (T) 1.5 kV DC
24 VDC 18 VDC 36 VDC 3.15 (T) 1.5 kV DC
48 VDC 36 VDC 72 VDC 3.15 (T) 1.5 kV DC
HI (125/250 VDC) 1
HI (110/230 VAC) 1
88 VDC
85 VAC
300 VDC
265 VAC
3.15 (T)
4 kV AC 5.5
kV DC
10W
Table 7 - Power Supply Specifications
NOTES:
1. This is the same power supply for both AC and DC.
2. (F) Denotes fast-acting fuse, (T) denotes time-delay fuse.
3. For continued protection against risk of fire, replace only with same type and rating of fuse.
5.3 Failsafe Relay Specifications
Load Circuit SELV TNV-2
MAX operating Voltage 30VDC 30 VAC 80VDC
MAX operating Current 1A 0.5A 0.3A
Isolation (between coil and contacts) 1800 V
rms
Table 8 - Failsafe Relay Specifications