2.1 Rack Mounting
The RSG2000 family of products can be rack mounted using the included rack
mount adapter assemblies shown in Figure 13. Secure the rack mount adapter to
the front side of the chassis using the included black PAN head Philips screws in
the positions shown in Figure 14. The entire chassis can then be mounted to a
standard 19” rack. An additional two rack mount adapters are included to
optionally secure the rear of the chassis in high-vibration or seismically active
locations.
Figure 13: RSG2000 Family 19” Rack Mount Adapters
Figure 14: Rack mount adapter mounting location
Note:
Since heat within the RSG2300 is channeled to the enclosure, it is recommended
that 1 rack-unit of space (1.75”) be kept unpopulated and free of equipment
above each RS2000 series product to allow for a small amount of convectional
airflow. Although forced airflow is not necessary, any increase in airflow will
result in a reduction of ambient temperature that will improve the long-term
reliability of all equipment mounted within the rack space.