Technical Specifications
IEC 61000-4-8 Magnetic Field Enclosure ports
40 A/m continuous,
1000 A/m for 1 s
N/A
D.C. Power ports
30% for 0.1s, 60% for
0.1s, 100% for 0.05s
N/A
IEC 61000-4-29
30% for 1 period, 60%
for 50 periods
N/A
IEC 61000-4-11
Voltage Dips &
Interrupts
A.C. Power ports
100% for 5 periods,
100% for 50 periods
N/A
Signal ports
2.5kV common, 1kV
diff. mode@1MHz
3
D.C. Power ports
2.5kV common, 1kV
diff. mode@1MHz
3
IEC 61000-4-12
Damped
Oscillatory
A.C. Power ports
2.5kV common, 1kV
diff. mode@1MHz
3
Signal ports
30V Continuous, 300V
for 1s
4
IEC 61000-4-16
Mains Frequency
Voltage
D.C. Power ports
30V Continuous, 300V
for 1s
4
IEC 61000-4-17
Ripple on D.C.
Power Supply
D.C. Power ports 10% 3
Signal ports
2kVac (Fail-Safe Relay
output)
N/A
D.C. Power ports 2kVac N/A
IEC 60255-5
Dielectric
Strength
A.C. Power ports 2kVac N/A
Signal ports
5kV (Fail-Safe Relay
output)
N/A
D.C. Power ports 5kV N/A
IEC 60255-5 H.V. Impulse
A.C. Power ports 5kV N/A
Note:
1. Only applicable to functional earth connections separated from the safety
earth connection
32
Rev100 © 2008 RuggedCom Inc. All rights reserved