15.4 Specifications
Item Standard or Performance Notes
Output capacity 1kVA/0.7kW
Cooling system Forced air cooling
Phases Single phase, 2-wire
Voltage
100,110,115,120V
-20% to +15% Double Conversion mode operation
±
5% Economy /Active Filter mode operation
±
10% Economy mode setting
User settable
(Rated voltage same as output voltage)
Frequency 50Hz or 60Hz
±
8%: Double Conversion mode operation
±
1, 3, 5%: Economy /Active Filter mode
operation
Power requirements 0.9kVA Max. capacity during battery charging
AC input
Input power factor 0.95 or more During rated output (*2)
Phases Single phase, 2-wire
Voltage 100, 110, 115, 120V User settable
Voltage regulation
Rated voltage
±
2%
Rated frequency 50Hz or 60Hz
Same as input frequency
(auto selection)
Frequency regulation
Rated frequency
±
1%: Double Conversion mode Setting
Rated frequency
±
1, 3, 5%: Economy/Active Filter
mode operation
1, 3, 5% selectable
Internal oscillator accuracy
±
0.5%
Voltage waveform Sine wave
Distortion factor of
voltage waveform
Linear load: 3% or less
100% rectifier load: 7% or less
During rated output
Rapid load
change
0%
⇔
100% at transient or output
switch
Power outage,
recovery
Rated voltage
±
5 %
During rated output
Transient
voltage
variation
Rapid input
voltage change
±
10% variation
Response time 5 cycles or less
Load power factor (lag) 0.7 (lag) Variation range 0.7 (lag) to 1.0
Overcurrent protection Auto switch to bypass circuit at 105% or more With auto return function
Inverter 105% 200ms
200% 30 seconds
AC Output
Overload
capability
Bypass
800% 2 cycles
Type Small sealed lead battery
Rated capacity
10 A
・
h (equivalent)
20 hour ratio
Number 2 (12V per battery) 2 in direct series
Batteries
Backup time
5 minutes (700W) 10 minutes (500W)
At 25°C (77°F) ambient temperature,
rated load
Generated heat 50W
Input leakage current 3mA or less
Operating environment
Ambient temperature: 0 to 40°C (32 to 104°F)
Relative humidity: 20 to 90%
(*3)
Acoustic noise 40 dB or less
1 m (approx. 40 inches) from UPS front
panel, 'A' characteristics (linear load)
(*1): The inverter is capable of operation synchronized with AC input and instantaneous
switchover provided that the AC input frequency is within
±
3% (or 1%, 3%, 5%,
selectable) of the rated frequency, and the AC input voltage is within +15% to-20% of the
rated voltage.
The UPS enters battery operation with the AC input frequency is outside the specified
range.
(*2): When input voltage waveform distortion is under 1%.
(*3): The UPS contains batteries. Battery service life will be foreshortened if the UPS is used
in an environment where the ambient temperature exceeds 30°C (86°F).
(*4): If grounded, the ground phase of the input and output must match according to UPS
specifications.
(*5): The above table lists standard specifications. Some specifications are different for units
with long backup times. For details, refer to the external battery specification
instruction manual.