Sanyo E11A202U Power Supply User Manual


 
12
6. Installation
CAUTION
When installing the UPS, carefully follow the instructions in this Instruction Manual.
Install the UPS on a stable surface that can bear the weight (29 kg, 63.93 lbs).
This surface should be flat, so the UPS cannot fall and cause bodily injury.
The possibility of vibration and shock should be minimized at the installation location.
All work that involves lifting the UPS, such as mounting it in a rack or attaching the
stand, should be carried out by at least 2 persons.
Be careful to avoid straining your lower back when moving and installing the UPS.
There is a danger that the UPS could fall or be dropped during relocation or
installation. Always hold the UPS securely by the upper edges. Failure to do so can
result in bodily injury or damage to the UPS.
6.1 Environment
Do not install the UPS in the following locations:
Where the ambient temperature exceeds 40°C (104°F).
For optimum battery life, install the UPS where the ambient temperature remains
between 20 to 25
°
C (68 to 77
°
F).
Where high humidity may occur.
Where corrosive gas or salt spray may be present.
Where it may be subject to vibration and shock.
Where dust may accumulate.
In a poorly ventilated rack (when the UPS is rack mounted).
6.2 Transporting
Transport the UPS in its original packing
carton, removing it only when near the
installation location.
6.3 Installation Space
During installation, provide the following space around the UPS.
At least 20 cm (about 8 inches) at the front as air intake space for cooling.
At least 20 cm (about 8 inches) at the back as air exhaust space for cooling
At least 1 meter (about 40 inches) at the front and 50 cm (about 20 inches) at the back
for maintenance when needed.
At least 1 meter (about 40 inches) from CRT displays to allow for slight leakage of
magnetic flux. Allow some space from devices which might be affected by magnetic
flux.
Installation Space for Vertical or Horizontal Installation Installation Space for Rack Mounting
Intake space
E11A
Exhaust space
At least 20cm
(Back)
(Front)
Rack
Maintenance space
At least 1m (40 in)
Maintenance space
A
t least 50 cm (20 in)
A
t least 20cm
(8 in)
(8 in)
Exhaust spac
A
t least
20cm (8 in)
A
t least 1m (40 in)
A
t least
20cm (8 in)
Intake space
Maintenance space
A
t least 50 cm (20 in)
Maintenance space
E11A
(Back)
Front
Exhaust space
CAUTION
When moving the UPS, do not let it tilt
more than 10 degrees to either side.
Tilting of more than 10 degrees can
cause the UPS to fall, resulting in
bodily injury.
If you must tilt the UPS more than 10
degrees, be careful not to let it fall.
The rack that
there are
ventilation
holes in the
door is
recommended.