17
−
③
Connect the input power plugs of the load devices to the output terminals.
MODEL Output terminal capacity Note
E11A202U001
125V 20A receptacle
×
4pcs.
(NEMA 5-20R)
The total output from all
output receptacles must not
exceed 2.0kVA
(
1.4kW
)
If you must make a single-wire
grounded connection, always
connect the ground phase to the
V terminal (phase) side.
E11A202U001J
125V 30A receptacle
×
1pcs.
(NEMA L5-30R)
The total output from all
output receptacles must not
exceed 2.0kVA
(
1.4kW
)
If you must make a single-wire
grounded connection, always
connect the ground phase to the
V terminal (phase) side.
7.2 External Interface Connections
Connect a computer or option card as required.
For details, see §5.3 “External Interfaces” and §10 “User Settings”.
Note
The CARD I/F and PC I/F connectors cannot be used at the same time.
7.2.1 Connections to the PC Interface (PC I/F)
Connect a computer to the PC I/F connector to control the UPS by using the supplied power
management software.
Install the power management software on the computer, and connect the computer to the
UPS with the supplied network cable. For more information, refer to the Install Guide or User
Guide in the CD-ROM of the power management software.
Before making the connection, check that item
⑤
“PC Interface mode” in §10.1 “Setup Menu
Item List” is set as follows.
Interface mode*: Workstation mode
7.2.2 Connections to the Card Interface (CARD I/F)
Connected an optional LAN interface card.
Before making the connection, check that item
⑤
“PC Interface mode” in §10.1 “Setup Menu
Item List” is set as follows
.
Interface mode*: Workstation mode
Note
This connector is for use with Sanyo option cards only. Contact your supplier for more
information about option cards.
* Use the control panel to set the interface mode. For more information, see item
⑤
Interface mode in
§10.1 “Setup Menu Item List”.
The total load connected to
the output terminals must
not exceed 20A.
For E11A202U001 For E11A202U001J
U
V(W)
E
(Or, N)
U
V(W)
E
(Or, N)