Schneider Electric AP9630 Network Card User Manual


 
UPS Network Management Card 2 User’s Guide10
Up Time: 0 Days 21 Hours 21 Minutes
Two fields report when you logged in, by date and time.
Date : 10/30/2009
Time : 5:58:30
• The User field reports whether you logged in through the Administrator or Device Manager account.
(The Read Only User account cannot access the command line interface.)
When you log on as Device Manager (equivalent to Device User in the user interface), you can access
the event log, configure some UPS settings, and view the number of active alarms.
User : Administrator
Main screen status fields.
• The Stat field reports the NMC status. The middle status varies according to whether you are running
IPv4, IPv6, or both, as indicated in the second table below.
Stat : P+ N+ A+
If P+ is not displayed, contact Customer Support. See “APC Worldwide Customer Support” on page 89.
P+ The operating system (AOS) is functioning properly.
IPv4
only
IPv6
only
IPv4 and
IPv6* Description
N+ N6+ N4+ N6+ The network is functioning properly.
N? N6? N4? N6? A BOOTP request cycle is in progress.
N– N6– N4- N6- The NMC failed to connect to the network.
N! N6! N4! N6!
Another device is using the IP address of the
NMC.
* The N4 and N6 values can be different from one another: you could, for example,
have N4– N6+.
A+ The application is functioning properly.
A– The application has a bad checksum.
A? The application is initializing.
A! The application is not compatible with the AOS.