Schneider Electric AP9630 Network Card User Manual


 
23UPS Network Management Card 2 User’s Guide
Description: This command is available for an AP9631 Network Management Card 2 with a connected Dry
Contact I/O Accessory (AP9810).
Example 1: To open the output, type:
uio -rc 2 open
Example 2: To view the status of the devices connected to a Dry Contact I/O Accessory that is installed in universal
input/ output port 2, type:
uio -st 2
ups
Some ups options are dependant on the UPS model. Not all configurations may support all options
of the ups command.
Access: Administrator, Device User
Description: Control the UPS and view status information.
Option Argument Description
-rc <UIO port #> open | close
Change the state of a connected output, and specify the UIO
(universal input/ output) port number.
-st
<UIO port #> |
<UIO port #>,
<UIO port #> |
<UIO port #>–<UIO port #>
View the status of the sensors connected to the Dry Contact
I/O Accessory. To view the status of a specific sensor or
several sensors, type their UIO port numbers.
-disc
<UIO port #> |
<UIO port #>,
<UIO port #> |
<UIO port #>–<UIO port #>
Identify new input contact or output relay connections.
Option Arguments Description
-c
off | graceoff | on |
reboot | gracereboot |
sleep | gracesleep
Configure UPS actions. See “Actions (for a single UPS and
Synchronized Control Groups)” on page 32 for detailed information.
-r start | stop
Initiate or end a runtime calibration. A calibration recalculates remaining
runtime and requires the following:
• Because a calibration temporarily depletes the UPS batteries, you can
perform a calibration only if battery capacity is at 100%.
• For some UPS devices, the load must be at least 7% to perform a
calibration.
-s start Initiate a UPS self-test.
-b enter | exit
Control the use of bypass mode. This command is model-specific and
may not apply to your UPS. See “Actions (for a single UPS and
Synchronized Control Groups)” on page 32 for detailed information.