SpectraLink 1738 Computer Hardware User Manual


 
SPECTRA SERIES 21
Figure 5.1: Spectra Zone Programming
5.5 ZONE DEFINITIONS
As demonstrated in Figure 5.1, sections [001] to [016] represent zones 1 through 16 respectively, where the first
digit in each of these sections represents the zone's definition. Also, refer to Zone Speed on page 25. To disable a
zone, clear the contents of the section corresponding to the desired zone by pressing the [
FORCE] key 3 times and
pressing [
ENTER]. There are 9 available Zone Definitions, which are described as follows.
5.5.1 ENTRY DELAY 1
Sections [001] to [016]: Zones 1 to 16, First Digit = 1
When the system is armed and a zone defined with Entry Delay 1 opens, the control panel will generate an
alarm after the programmed Entry Delay 1 Timer elapses. This is to provide users with enough time to
enter the protected area and disarm the system. To program the Entry Delay 1 Timer, key in the desired 3-
digit delay value (000 to 255 seconds, Default = 45 seconds) into section [069]. Entry Delay zones are
commonly used at the entry/exit points of the protected area (i.e. front/back door, garage, etc.). Using
different Entry Delays (see Entry Delay 2) is useful when, for example, one entry point requires a longer
delay than the other entry point or in a partitioned system where each partition may require a different
Entry Delay.
Press the
[
ENTER
]
key
Key in
3-digit
[
SECTION
]
Zone Definition
First Digit
Zone Options
Feature Select
Enter the
[
INSTALLER
CODE
]
Zone Definitions
1 -
Entry Delay 1
2 -
Entry Delay 2
3 -
Follow
4 -
Instant
5 -
24Hr. Burglary
6 -
24Hr. Buzzer
Additional definitions for on-board
terminals:
7 -
Keyswitch
8 -
24Hr. Fire
9 -
24Hr. Delayed Fire
Zone Options
[1]
Auto Zone Shutdown Enabled
[2]
Bypass Enabled
[3]
Stay Zone
[4]
[5]
Zone Alarm Type
off off Audible Alarm (steady)
off on Audible Alarm (pulsed)
on off Silent Alarm
on on Generates only a report
[6]
Intellizone
[7]
Delay alarm transmission
[8]
Force Zone
Keyswitch Options
[1]
off = Maintained
on = Momentary
[2]
off = Regular Arm
on = Stay Arm
Select
one
Press
[
ENTER
]
[001]
= Zone 1
[009]
= Zone 09
[002]
= Zone 2
[010]
= Zone 10
[003]
= Zone 3
[011]
= Zone 11
[004]
= Zone 4
[012]
= Zone 12
[005]
= Zone 5
[013]
= Zone 13
[006]
= Zone 6
[014]
= Zone 14
[007]
= Zone 7
[015]
= Zone 15
[008]
= Zone 8
[016]
= Zone 16
Zone Partition
Assignment
Second Digit
Select
one
Zone Partition Assignment
1-
Zone Assigned to Partition 1
2-
Zone Assigned to Partition 2
3-
Zone Assigned to Both Partitions
Keypads beep twice