30 REFERENCE & INSTALLATION MANUAL
PART 7: ALARM OPTIONS
7.1 BELL CUT-OFF TIMER (5 minutes minimum for CUL installations)
Section [073] = Partition 1, [074] = Partition 2
000 = Disabled, 001 to 255 minutes, Default = 4 min.
After an audible alarm, the bell or siren will stop upon disarming of the partition or when the Bell Cut-Off Timer has
elapsed, whichever comes first.
7.2 RECYCLE ALARM
After the Bell Cut-Off Timer and the Recycle Delay have elapsed, the control panel will re-verify the zone status. If
there are any open zones, the control panel will generate another alarm. In one armed period, the control panel will
repeat this sequence the number of times defined by the Recycle Counter.
7.2.1 RECYCLE ALARM DELAY
Section [090]
000 = disabled, 001 to 255 minutes, Default = disabled
The Recycle Delay determines the amount of time after Bell Cut-Off that the control panel will wait before
re-verifying zone status.
7.2.2 RECYCLE COUNTER
Section [091]
000 = disabled, 001 to 255, Default = disabled
The Recycle Counter determines the number of times the control panel will re-verify the zone status after
Bell Cut-Off in one armed period.
7.3 TAMPER RECOGNITION
Section [132]: Zone Options
[1] OFF / [2] OFF: Tamper Recognition Disabled (default)
If the system is armed or disarmed
, the control panel will display the zone as open in the keypad display, but will
not generate an alarm. This option is not permitted on UL systems.
[1] OFF / [2] ON: Trouble Only
If the system is armed
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm
Types setting (see page 24).
If the system is disarmed
and a tamper wiring failure occurs on a zone, a Tamper/
Zone Wiring Failure will appear in the keypads’ Trouble Display (see page 50) and the control panel will transmit the
appropriate Zone Tamper report code (see page 34).
[1] ON / [2] OFF: Silent Alarm
If the system is armed
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm
Types setting (see page 24). In a disarmed system, it functions the same as the Trouble Only setting, but it will also
generate a silent alarm. A silent alarm will not trigger any bells or sirens, but the system will have to be disarmed.
[1] ON / [2] ON: Audible Alarm
In an armed system and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm
Types setting (see page 24). In a disarmed system, it functions the same as Trouble Only setting, except it will also
generate an audible alarm.
7.3.1 TAMPER BYPASS OPTIONS
Section [132]: Zone Options
Option [3] OFF = Will generate a tamper if detected on a bypassed zone (default)
Option [3] ON = Tampers on bypassed zones will be ignored
With option [3] on, the Tamper Recognition feature follows the zone bypass definition. This means the
control panel will ignore any tampers detected on a bypassed zone. With option [3] off, Tamper