SpectraLink 1738 Computer Hardware User Manual


 
SPECTRA SERIES 39
Option [5] ON = Dialer will hang-up if no dial tone is present after 16 seconds
8.12 MAXIMUM DIALING ATTEMPTS
Section [081]
001 to 016 attempts, Default = 8 attempts
The value programmed in section [081] determines how many times the control panel will re-dial the same Central
Station Telephone Number before proceeding to the next number.
8.13 DELAY BETWEEN DIALING ATTEMPTS
Section [082]
000 to 255 seconds, Default = 20 seconds
This delay determines the amount of time the control panel will wait between each dialing attempt.
8.14 ALTERNATE DIAL OPTION
Section [136]: Dialer Options
Option [4] OFF = Alternate Dial Disabled (default)
Option [4] ON = Alternate Dial Enabled
With option [4] off, the control panel will dial the backup telephone number programmed in section [153] after all
attempts to one Central Station Telephone Number have failed (see section 8.12). With option [4] on, the control
panel will dial the backup telephone number after every failed attempt.
8.15 RECENT CLOSE DELAY
Section [085]
000 to 255 seconds, Default = no delay
If after having armed the system, an alarm is generated within the period defined by the Recent Close Delay, the
control panel will attempt to transmit the Recent Close report code programmed in section [195].
8.16 AUTO TEST REPORT
Sections [087]
000=disabled, 001 to 255 days, Default = disabled
Section [110]: Time (HH:MM)
The control panel will transmit the Test Report report code programmed into section [211] after the number of days
programmed into section [087] has elapsed at the time programmed into section [110]. Use the 24-hour clock to
program the time (i.e. 6:30PM = 18:30). The first Test Report will be transmitted within 24 hours after the feature is
enabled at the time programmed in [110].
Example: Section [087] = 005 and section [110] = 13:00. The first Test Report will be sent at 1 PM that day and then
the report will be sent every 5 days at 1 PM.
8.17 POWER FAILURE REPORT DELAY
Section [086]
001 to 255 minutes, Default = 15 minutes
The control panel will transmit the AC Failure report code programmed in section [205] after the Power Failure
Report Delay period has elapsed.