Texas Memory Systems RamSan-500 Power Supply User Manual


 
RamSan-500 User’s Manual 42 of 48
OFF No Power, zone not present
Because each Flash zone is independent of the other, the status of each
zone may differ.
W
ARNING
R
EMOVING A FLASH MODULE WHILE IT IS POWERED ON MAY CAUSE
IRREVERSIBLE
DAMAGE TO THE MODULE
.
O
NLY
R
EMOVE
A
F
LASH
M
ODULE IF BOTH STATUS INDICATOR
LED
S ARE
O
FF
.
5.3.1
5.3.15.3.1
5.3.1 Flash
Flash Flash
Flash M
MM
Module
odule odule
odule F
FF
Failure
ailureailure
ailure
In addition to the error correct features built into the Flash module,
the Flash modules are protected from a complete Flash module failure
by a RAID configuration. If only a single module fails in a RAID, all
data in the array will be preserved. You should replace the bad Flash
module right away. If the system detects a bad Flash module, it will
note the bad module by illuminating the red LED on the front of the
module.
System Status: WARN
Errors: Flash Module
Degraded
The front panel display will
register a warning stating that
one or more modules have
been degraded. A degraded
module functions correctly, but
a degraded array cannot
tolerate another Flash module
failure without data loss.
You can also get information about the state of the Flash modules from
the Web monitor.