Battery run time is less than expected.
The AC load will not operate. The
FAULT light is on.
Possible Cause Suggested Remedy
The AC product power
consumption is higher than rated.
Use a larger battery to make up for
the increased power requirement.
The battery is old or defective. Replace the battery.
The battery is not being charged
properly.
Some chargers are not able to fully
recharge a battery. Make sure that
you use a powerful charger.
Power dissipation in DC cables. Use shorter/heavier DC cables.
Possible Cause Suggested Remedy
The AC product(s) connected are
rated at more than the inverter’s
continuous power rating;
overload shutdown has occurred.
Use a product with a power rating
less than the inverter’s continuous
power rating (see
Table 1 on
page 30).