3Com Prestige Series Power Supply User Manual


 
Installation
42
Powerware
®
Prestige Series Installation andOperator’sManual forIBM Applications (3000 VA) Uncontrolled Copy
UPS with PPDM Startup
To st art up the U PS :
1. If you are connecting the UPS to an AS/400, the QUPSDLYTIM
system value for the UPS Monitoring feature should be set. See
“UPS Monitoring” on page 52 for instructions.
2. Confirm the Bypass switch on the PPDM rear panel is in the
NORMAL position.
3. Steps 4 through 8 are for changing the output voltage. The
output voltage is factory-configured for 230V. If you do not
need to change the output voltage, skip to Step 9.
Use the following table to select the correct output voltage
according to your PPDM.
PPDM Model Number UPS Voltage Selection*
5-15R PPDM 208: 120/208 208
5-15R PPDM 208: 120/240 208
5-15R PPDM 208: 120 208
5-15R PPDM 240: 120/240 Set to 220V for 110/220V PPDM output
Set to 230V for 115/230V PPDM output
Set to 240V for 120/240V PPDM output
5-15R PPDM 240: 120 Set to 220V for 110V PPDM output
Set to 230V for 115V PPDM output
Set to 240V for 120V PPDM output
5-15R/6-15R PPDM: 208 208
5-15R/6-15R PPDM: 240 240
IEC 320-C13 PPDM Set to 220V for 220V PPDM output
Set to 230V for 230V PPDM output
Set to 240V for 240V PPDM output
The UPS output voltage should be set according to local mains voltage.