Specifications
68
Powerware
®
Prestige Series Installation andOperator’sManual forIBM Applications (3000 VA) Uncontrolled Copy
Prestige 3000 UPS Technical Specifications
Input Voltage Range 160 to 276 Vac
Input Power Factor 0.95 Typical
Frequency Range 50/60 Hz ±3 Hz
Surge Protection IEC 801-4
Output Waveform Sine wave
Output Voltage
(without PPDM)
200/208/220/230/240 Vac ±3%
Online (BTUs) 978
On Battery (BTUs) 1468
Common Mode Noise
Rejection
>60 dB @ 100 kHz
Transverse Mode Noise
Rejection
>80 dB @ 100 kHz
Input Cord Detachable 2-meter cord
Outlets (UPS Cabinet) IEC 320 (1)
Output Voltages and Outlets
(with PPDM)
120/208V: 5-15R (2), 6-15R (2), IEC 320-C19 (1)
120/240V: 5-15R (2), 6-15R (2), IEC 320-C19 (1)
220/230/240V: IEC 320-C13 (6), IEC 320-C19 (1)
120/208V: L6-30R (1), 5-15R (4)
120/240V: L6-30R (1), 5-15R (4)
Batteries (10) per cabinet 12 Vdc, 5 Ah, maintenance-free rechargeable lead acid
Battery Cabinet 120 Vdc
Operating Environment Temperature: 10 Cto40C
(50
F to 104 F)
Humidity: 5 to 95%
(noncondensing)
Agency Approvals Safety: EN50091-1
UL 1778
cUL
EMC: FCC Part 15 Class A
EN50091-2