ADC Power Distribution Products Power Supply User Manual


 
ADCP-80-526 • Issue 6 • December 2006
Page 18
© 2006, ADC Telecommunications, Inc.
4.2 Mounting Fuse Platform on Rack
The fuse platform can be mounted in either a 19- or 23-inch (48.26 or 58.42 cm) wide rack. Two
sets of mounting brackets, one set for 19-inch racks and one set for 23-inch racks, are provided
with the fuse platform.
Eight 5/16-inch (7.936 mm) long, thread-forming, Phillips-drive, 8-32 flat-head screws are
provided for attaching the mounting brackets to the panel. Four 3/8-inch (9.53 mm) long,
Phillips-drive, 12-24 pan-head screws (with flat washers) are provided for attaching the
mounting brackets to the equipment rack.
Use the following procedure to attach the mounting brackets to the fuse platform and to install
the fuse platform in the equipment rack:
1. Select the set of mounting brackets (19- or 23-inch) that correspond to the width of the
equipment rack into which the fuse platform will be installed.
2. Orient the mounting brackets as shown in Figure 13.
3. Attach the brackets to the sides of the fuse platform using the eight 5/16-inch (7.94 mm)
long flathead screws provided. Tighten screws to 15 pound force-inches (1.7 Newton
meters) of torque to insure grounding.
Figure 13. Mounting Brackets
Note: A fuse platform with the cable management bar attached may exceed the 12 inch
(305 mm overall depth objective described in GR-63 CORE, 02-14.
Caution: When attaching the mounting brackets to the fuse platform, use only the 5/16-inch
(7.94 mm) long, thread-forming, flat-head screws supplied with the fuse platform. Use of any
other hardware could cause contact with internal parts of the fuse platform. If parts are
missing, contact ADC to order replacement parts.
18864-A
19-INCH RACK
INSTALLATION
23-INCH RACK
INSTALLATION
5/16-INCH (7.94 MM)
8-32 FLAT-HEAD
THREAD-FORMING
SCREWS
TIGHTEN MOUNTING SCREWS
TO 15 POUND-FORCE INCHES
(1.7 NEWTON METERS) OF TORQUE