mentary equipment grounding conductor shall be in compli-
ance with the rules for terminating bonding jumpers at Part K
or Article 250 of the National Electrical Code, ANSI/NFPA 70.
Termination of the supplementary equipment grounding con-
ductor is permitted to be made to building steel, to a metal
electrical raceway system, or to any grounded item that is per-
manently and reliably connected to the electrical service equip-
ment ground.
Bare, covered, or insulated grounding conductors are accept-
able. A covered or insulated grounding conductor shall have a
continuous outer finish that is either green, or green with one
or more yellow stripes.
The supplemental grounding conductor shall be connected to
the equipment using a number 8 ring terminal. The terminal
should be fastened to the grounding lug provided on the rear
panel of the equipment. The ring terminal should be installed
using the appropriate crimping tool (AMP P/N 59250 T-EAD
Crimping Tool or equivalent).