American Power Conversion MX28B2400 Power Supply User Manual


 
MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual Page 38
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Battery High Temperature
Alarm
Security Level {1}
[BATT/SET-ALM]
The output relay energized if the battery
temperature exceeds the Battery High
Temperature threshold.
Batt HT Alm m+
Minor
Battery High Temperature
Threshold
Security Level {1}
[BATT/SET-ALM]
Battery Temperature is temperature measured at
the battery probe. An alarm is generated if the
battery temperature exceeds this value.
Batt HT Thr m+
70.0 C
Battery High Voltage Alarm
Security Level {1}
[BATT/SET-ALM]
The output relay energized if the DC output
voltage rises above the battery high voltage
threshold.
Batt HV Alm m+
Minor
Battery High Voltage Threshold
Security Level {1}
[BATT/SET-ALM]
An alarm will be reported if temperature is lower
than the temperature entered.
An alarm is generated if the DC output voltage
rises above this value.
Batt HV Thr m+
-58.00 V
Battery Low Temperature
Alarm
Security Level {1}
[BATT/SET-ALM]
The output relay energized if the Battery
Temperature drops below the battery Low
Temperature threshold.
Batt LT Alm m+
Minor
Battery Low Temperature
Threshold Security Level {1}
[BATT/SET-ALM]
Battery Temperature is temperature measured at
the battery probe. An alarm is generated if the
battery temperature drops below this value.
Batt LT Thr m+
0.0 C
Battery Low Voltage Alarm
Security Level {1}
[BATT/SET-ALM]
The output relay energized if the DC output
voltage drops below the battery low voltage
threshold.
Batt LV Alm m+
Minor
Battery Low Voltage Threshold
Security Level {1}
[BATT/SET-ALM]
An alarm is generated if the DC output voltage
drops below this value.
Batt LV Thr m+
-44.00 V
Battery Maximum Recharge
Current
Security Level {1}
[BATT/PARAM]
One of three parameters that control the DC
output voltage. If Battery Current surpasses the
Maximum Battery Recharge Current, the DC
output voltage will be reduced (the system limits
the charging current to this programmable value).
Batt Max Rechm+
50 A
Battery Temperature
{Status Only}
[STATUS]
Battery temperature measured by the system
controller at the optional battery temperature
sensor probe.
Batt Temp +
25.2 C
Circuit Breaker 1 Alias
Security Level {1}
[MODULES/CIRBKR/ALIAS]
Circuit Breaker 24 Alias
Security Level {1}
[MODULES/CIRBKR/ALIAS]
An alternate name (alias) that can be assigned to
a circuit breaker if desired.
An alternate name (alias) that can be assigned to
a circuit breaker if desired.
Cir Bkr 1 m+
-48V
Cir Bkr 72 m+
-48V