American Power Conversion MX28B2400 Power Supply User Manual


 
MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual Page 42
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Output Relay 1 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Output Relay 6 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Delay between sensing of the alarm condition and
activation of Output Relay 1. An alarm condition
must exist for longer than the delay to be
activated.
Delay between sensing of the alarm condition and
activation of Output Relay 6. An alarm condition
must exist for longer than the delay to be
activated.
Out-Rly 1 Dly m+
0 sec
Out-Rly 6 Dly m+
0 sec
Output Relay Major Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the
major Relay if desired.
Relay Major m+
Major
Output Relay Minor Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the
Minor Relay if desired.
Relay Minor m+
Minor
PIN 1 change
Security Level {2}
[SYSTEM/SETUP]
Permanently change password (PIN) that permits
security Level 1 parameter changes - limited
access.
PIN m+
1111
PIN 2 Change
Security Level {2}
[SYSTEM/SETUP]
Permanently change password (PIN) that permits
security Level 2 parameter changes - unlimited
access.
PIN 2 m+
2222
PIN Entry
Security Level {0}
[PIN]
Screen for entry of the active password (PIN).
Before any changes can be made, the correct pin
for the desires security level must be entered.
Level 0 – full read access. Level 1 –full read and
limited write access. Level 2 – full read and write
access.
PIN m+
0000
Rectifier Communications Fail
Timeout
Security Level {1}
[MODULES/RECT/PARAM]
The maximum rectifier communications response
time allowed before a communications failure is
declared.
RectFailComm m+
1 min
Rectifier Configuration Alarm
Security Level {1}
[SYSTEM/SET-ALM]
The output relay energized if the rectifier
configuration differs from its stored configuration.
This occurs if a rectifier is added after
configuration.
Rect Cfg Alm m+
Minor
Rectifier Current Limit Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]
The output relay that is energized or special
rectifier alarm group n of N that occurs when a
rectifier has been forced into the current limited
mode.
Rect CL Alm m+
n of N
Rectifier Current Limit Alarm
Status
{Status Only}
[MODULES/RECT/INFO]
The status will be “ON” if the rectifier has been
forced into its current limited mode. NOTE
: This
information can be viewed for each rectifier
installed by using the horizontal arrow keys.
Rect 1 CL #
OFF
Rectifier Current Output Status
{Status Only}
[MODULES/RECT/INFO]
A display of the DC output current for the
individual rectifier. NOTE
: This information can
be viewed for each rectifier installed by using
the horizontal arrow keys.
Rect 1 Curr #
24.9 A