American Power Conversion MX28B2400 Power Supply User Manual


 
MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual Page 39
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Circuit Breaker 1 Tripped
Security Level {1}
[MODULES/CIRBKR/SET-
ALM]
Circuit Breaker 24 Tripped
Security Level {1}
[MODULES/CIRBKR/SET-
ALM]
An alarm that indicates Circuit Breaker 1 is
tripped.
An alarm that indicates Circuit Breaker 24 is
tripped.
Cir Bkr 1 Alm m+
Major
Cir Bkr 72 Almm+
Major
Compensation High Knee
Security Level {1}
[BATT/COMP]
The temperature compensation high knee is the
point above which there is no additional battery
voltage compensation for further increases in
temperature.
Comp Hknee m+
40.0 C
Compensation Low Knee
Security Level {1}
[BATT/COMP]
The temperature compensation low knee is the
point below which there is no additional battery
voltage compensation for further decreases in
temperature.
Comp Lknee m+
0.0 C
Compensation Method
Security Level {1}
[BATT/COMP]
One of three parameters that control the DC
output voltage. Activate “ON” or de-activate “OFF”
battery temperature compensation.
Comp Method m+
OFF
Compensation Temperature
Coefficient
Security Level {1}
[BATT/COMP]
Temperature compensation coefficient between
low knee and high knee in mV/cell/°C.
(Compensation equals zero at 25°C.)
Comp TC m+
- 3.00mV
Control Unit Revision
{Status Only}
[SYSTEM/SETUP]
Hardware revision level of the control unit. This
parameter cannot be changed.
Cntrl Rev +
000002
Date
Security Level {1}
[SYSTEM/DATE]
Internal system calendar date. Used as a date
stamp in the event log.
Date m+
DEC 16 1999
Display Type
{Status Only}
[SYSTEM/SETUP]
Type number for the control unit display. This
parameter cannot be changed.
Display Type +
000255
Fahrenheit Scale
Security Level {1}
[SYSTEM/SETUP]
Enables selection of Fahrenheit or Celsius
temperature scale (Fahrenheit “OFF” displays
readings in °C).
Fahrenheit m+
OFF
Firmware Version
{Status Only}
[SYSTEM/SETUP]
Version number of the control unit firmware.
NOTE: Actual firmware version number
displayed is the current version as of the date
of manufacture. This parameter cannot be
changed.
FW Version +
000189
FUSE 1 Alias
Security Level {1}
[MODULES/FUSE/ALIAS]
FUSE 8 Alias
Security Level {1}
[MODULES/FUSE/ALIAS]
An alternate name (alias) that can be assigned to
a FUSE Fuse 1 if desired.
An alternate name (alias) that can be assigned to
a FUSE Fuse 8 if desired.
Fuse 1 m+
-48V
FUSE 16 m+