American Power Conversion S15BLK Power Supply User Manual


 
1-7
LOW BATTERY Status Indicator
When lit (orange) it indicates the battery pack charge level is low. When
this indicator turns on it indicates that there is minimum, time remaining.
The purpose of this warning is to allow time to shut off power to the
equipment before the battery pack is fully discharged. The user can set the
value (from 2 to 25 minutes). When the indicator is lit, leave the unit
plugged in to allow batteries to recharge.
Note: The unit does not have to be powered on for batteries to
recharge.
LINE OK Status Indicator
When this indicator is lit, it indicates the input voltage from the utility is
within the acceptable range (90V to 144V) for the S10 and S15. If it is not
lit, the input voltage from the utility is outside the acceptable range, and it
will go into boost mode or trim mode to compensate for the (low or high)
incoming AC line voltage.
FILTERING Status Indicator
When this indicator is lit, it notifies the user that the electromagnetic
interference and radio frequency interference (EMI and RFI) noise
reduction circuit is active.
OVERLOAD Status Indicator
When lit (red) the unit is overloaded; unplug the devices connected to the
unit one at a time until the indicator is no longer lit.
Down Arrow Push Button
This pushbutton is used to change (decrease or turn off) parameters for
various user-selectable settings such as: Audible Alarms, Sensitivity,
Display Dimmer, LED Dimmer, Go To Bat If, Outlet 1 & 2 Delay
(in seconds), Low Bat Warning, Bat Rep Date, and so on.
On/Off Switch
This switch controls power to all of the 12 outlets located on the rear of
the unit. APC recommends the unit be left ON at all times. Control power
to your system components as you normally would, instead of using the
S10/S15 On/Off Switch.
6
7
8
9
10
11