APC 6739380EN/JC Power Supply User Manual


 
6739380EN/JC - Page 13
3
7
4'
4
1
1312
5
10
8
9
11
2
22 2
22
6
Inverter cubicle
250 to 400kVA UPS or frequency converter
front view, doors open, protective covers removed
Fig. 18
600kVA UPS or frequency converter
Fig. 20
front view, doors open, protective covers removed
The rated outputs for
MGE
TM
Galaxy
TM
6000 UPS’s (without
parallel connection) or frequency
converters are 160, 200, 250, 300, 400,
500, 600 kVA.
Legend for figures 18 to 21:
1-rectifier-charger (RC) module
2-inverter stack modules
3-rack for electronic control boards
4-static switch module (Single-unit or
modular UPS)
4' - output static switch module
(modular UPS, frequency converter or
parallel UPS with SSC)
5-RC input fuses FU1-2-3
6-Mains 1 input switch Q1
7-protection fuses FU8 for the
Mains 2 resistance/capacitance voltage
surge protection network
8-Mains 2 input switch Q4S (Single-
unit or modular UPS)
9-maintenance bypass switch Q3BP
(Single-unit or modular UPS)
10- output switch Q5N
11- inverter output fuses FU 5-6-7
12- "Media Contacts 9" remote
indications board
13- additional "Media Contacts 15"
remote indications board (optional).
22
6
8 9 10
3
1
7
5
2
4'
4
11
12
13
Description of MGE
TM
Galaxy
TM
6000 cubicles
450 to 500kVA UPS or frequency converter
front view, doors open, protective covers removed
Fig. 19
22
6
8 9 10
3
1
7
5
2
4'
4
11
12
13