USER’S GUIDE
switched rack pdu
33
Switched Rack PDU Settings
Configure Load Thresholds
Web interface. Select Switched Rack PDU from the navigation menu
and and click the Configure button in the Load Management section. Set
the Overload Alarm thresholds, Near Overload Warning thresholds, Low
Load Warning thresholds, and Outlet Restrictions for each phase. Press
the Apply button in that section to set the selected values.
Control console. Select Phase Monitor/Configuration on the Device
Manager menu. Select a phase (for 3-phase units). Select Low Threshold
(amps), Warning Threshold (amps), or High Threshold (amps) and
press
ENTER.
To set the overload outlet restriction, select
Outlet Restriction Configuration
on the Device manager menu. For 3-phase units, select a phase to display
and change the Outlet Phase Restriction.
Setting Description
Overload Alarm
Threshold
Set the number of amps that will cause an overload of this
phase.
Near Overload
Warning
Threshold
Set the number of amps at which to generate a warning that the
PDU is nearing overload of a phase.
Low Load
Warning
Threshold
Set the low threshold, in amps, for the current drawn from this
phase during normal operation. A load at or below this level
generates a warning.