APC VS 50 Power Supply User Manual


 
Magnum VS –48 Vdc User’s Manual Page 40
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION SETTINGS (Default
settings in BOLD)
Current Limit Alarm Status
{Status Only}
[Power Modules/Rectifiers]
The status will be “ON” if the rectifier has
been forced into its current limited mode.
Status Only
Date
[System/Date & Time]
Internal network management card
calendar date. Used as a date stamp in
the web card event log.
Current Date
Description 1
[System/DC Parameters]
Power plant identification - first line.
Description 2
[System/DC Parameters]
Power plant identification - second line. Magnum VS
This is not user edit-able.
Description 3
[System/DC Parameters]
Power plant identification - third line. Power System
This is not user edit-able.
Fail Safe
[Power Modules/Rectifiers]
If the rectifiers fail to communicate with
the system, the rectifiers will output this
pre-defined voltage.
This feature is supported
by the standard SNMP
card monitor, but is not
supported by this dc
system.
FUSE 1 Alias
[Distribution/Fuses]
FUSE 1 Alias
[Distribution/Fuses]
An alternate name (alias) can be
assigned to Fuse 1 if desired. This
feature is supported by the standard
SNMP card monitor, but is not supported
by this dc system.
FUSE 1
FUSE 16
FUSE 1 Blown
[Distribution/Fuses]
FUSE 4 Blown
[Distribution/Fuses]
Defines the output relay that is energized
when F1-4 is blown.
Defines the output relay that is energized
when F13-16 is blown.
Ignore, Minor, Major
Output Relay 1-6
Ignore, Minor, Major
Output Relay 1-6
Fuse 5-16 is not used in
this system
Hardware Battery Current
Alarm
[Batteries Parameters]
Defines the output relay that is energized
if there is a hardware failure in the
battery current monitoring function. This
feature is supported by the standard
SNMP card monitor, but is not supported
by this dc system.
Ignore, Minor, Major
Output Relay 1-6
Hardware Battery Temperature
Alarm
[Batteries Parameters]
Defines the output relay that is energized
if there is a hardware failure in the
battery temperature monitoring function.
Program to Ignore if no battery
temperature probe is connected to J410.
Ignore, Minor, Major
Output Relay 1-6
Hardware LVD Alarm
[Batteries/LVD]
Defines the output relay that is energized
if there is a conflict between the
commanded and sensed positions of the
LVD contactor. This feature is supported
by the standard SNMP card monitor, but
is not supported by this dc system.
Ignore, Minor, Major
Output Relay 1-6