APC VS 50 Power Supply User Manual


 
Magnum VS –48 Vdc User’s Manual Page 53
9 Specifications
The overall system specifications can vary, depending upon the number of rectifier modules.
Note that some specification items are provided on a “per rectifier” basis and must be combined
or totaled for a given system configuration.
9.1. AC Input
TWF0500H54B Rectifier
Input Voltage Range 85 – 264 Vac
AC Frequency Range 47 – 63 Hz
Apparent Power Factor 99% Typical, 98% Minimum
Input Current (per Rectifier) 5.5 A @ 115Vac
3.7 A @ 230Vac
Turn on Time 2 Seconds
Magnum VS 50 Power System
Input Voltage Range 85 – 264 Vac
AC Frequency Range 47 – 63 Hz
Apparent Power Factor 99% Typical, 98% Minimum
Input Current 27.5 A @ 115 Vac
18.5 A @ 230 Vac