APC VS 50 Power Supply User Manual


 
Magnum VS –48 Vdc User’s Manual Page 41
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION SETTINGS (Default
settings in BOLD)
Hardware System Voltage
Alarm
[Power Modules/Rectifiers]
Defines the output relay that is energized
if there is a hardware failure in the
system voltage monitoring function.
Ignore, Minor, Major
Output Relay 1-6
Hardware Temperature Alarm
[System/DC Parameters]
Defines the output relay that is energized
if there is a hardware failure in the
system temperature monitoring function.
Ignore, Minor, Major
Output Relay 1-6
High Temperature Alarm
[System/DC Parameters]
Defines the output relay that is energized
if the System Temperature exceeds the
system high temperature threshold. Not
the same as battery temperature alarm.
Ignore, Minor, Major
Output Relay 1-6
High Temperature Threshold
[System/DC Parameters]
Ambient temperature measured inside
the controller. An alarm will be reported
if temperature is higher than the
temperature entered. Not the same as
battery temperature threshold.
0 °C – 100 °C, 70.0 °C
High Voltage alarm
[Power Modules/Rectifiers]
Defines the output relay that is energized
if the System Voltage is above the
System High Voltage threshold. Not the
same as battery voltage alarm.
Ignore, Minor, Major
Output Relay 1-6
High Voltage Threshold
[Power Modules/Rectifiers]
DC voltage measured by the controller.
An alarm will be reported if voltage is
higher than the voltage entered. Not the
same as battery voltage threshold.
-60 V – -40 V, -58.00 V
Imbalance Alarm
[Power Modules/Rectifiers]
An alarm will be generated if the rectifiers
do not current share. This feature is
supported by the standard SNMP card
monitor, but is not supported by this dc
system.
Ignore, Minor, Major
Output Relay 1-6
Input Relay 1
[I/O/Input]
Input Relay 4
[I/O/Input]
Defines the output relay that is energized
when an external contact closure or
opening at the Input Relay 1 connection
changes state.
Defines the output relay that is energized
when an external contact closure or
opening at the Input Relay 4 connection
changes state.
Ignore, Minor, Major
Output Relay 1-6
Ignore, Minor, Major
Output Relay 1-6
Input Relay 1-4 Alias
[I/O/Input]
This feature is supported by the standard
SNMP card monitor, but is not supported
by this dc system.
Input 1-4
Input Relay 1-4 Delay
[I/O/Input]
This feature is supported by the standard
SNMP card monitor, but is not supported
by this dc system.
0.00 Seconds
Low Temperature Alarm
[System/DC Parameters]
Defines the output relay that is energized
if the System Temperature is below the
System Low Temperature threshold. Not
the same as battery temperature alarm.
Ignore, Minor, Major
Output Relay 1-6