Belkin AVU1500 Power Supply User Manual


 
Belkin PureAV Hybrid AVU1500 UPS
55
Using Your AVU1500 with a
Home Automation System (optional)
Check Sum
Sum the bytes from “Header” to “Data”. Overflow ignored.
Notification
AVU models have the ability to send UPS data to PC regardless of any
pending polling commands from computer.
Power Configuration Controls (UsagePage=0x86)
Report ID# Usage (usage ID) Byte # Unit Comment
1 } ConfigVoltage (0x40) 1 Volt R
2 } ConfigFrequency (0x42) 1 Hertz R
3 } ConfigApparentPower (0x43) 2 VA R
4 } ConfigBatteryVolt (0x44) 2 Volt R
ConfigVoltage: Nominal value of the voltage.
ConfigFrequency: Nominal value of the frequency.
ConfigApparentPower: Nominal value of the apparent power.
ConfigBatteryVoltage: Nominal value of the battery voltage.
Power Device Identification (UsagePage=0x86)
Model String Index: Index of a string descriptor describing model
names string. The UPS Model String may contain several model
names, each name is separated by a “/”. If this command comes
from the RS232, then UPS returns the Model String rather
than Index.
Model String Offset: Offset of the UPS model name in the model
names string.
UPSType:
Low 4 bits Result
0: On-Line
1: Off-Line
2: Line-Interactive
3: Simple On-Line
4: Simple Off-Line
5: Simple Line-Interactive
High 4 bits Result
Indicates the firmware version
Report ID # Usage (usage ID) Byte # Unit Comment
13 }Model String Index (0x75) 1 R
14 }Model String Offset (0x76) 1 R
15 }UPSType (0x7C) 1 R