Compaq 3000 Series Power Supply User Manual


 
4-4 Compaq 3000 Series UPS Operation and Reference Guide
Table 4-1
Configuration Parameters/LED Indicators
Parameter
(LED)
Parameter
Name
LED 16
Status
Explanation
1 120/230 Nom On
1
Nominal utility voltage level is
120/230 VAC.
(Default for R3000, R3000h,
and R3000h-Int)
2 110/220 Nom On
1
Nominal utility voltage level is
110/220 VAC.
3 127/240 Nom On
1
Nominal utility voltage level is
127/240 VAC.
10 100/208 Nom On
1
Nominal utility voltage level is
100/208 VAC.
(Default for R3000j and R3000h-NA)
4 Extended
Voltage
On UPS will supply utility power if the utility
voltage is within +20% to –35% of the
nominal voltage. If the utility voltage is
outside this range, the UPS will supply
battery power.
(This option not available on the R3000j
and R3000h-NA)
Off
(default)
UPS will supply utility power if the utility
voltage is within ±20% of the nominal
voltage. If the utility voltage is outside this
range, the UPS will supply battery power.
5 Wiring
Fault
On
(default)
Enables an audio alarm if ground is
missing, or if line and neutral connections
have been reversed.
(This option not available on the R3000j
and R3000h-NA)
Off Disables the audio alarm for this event.
(Default for R3000j and R3000h-NA)
6 Low
Battery
On
(default)
Enables an audio alarm 3 minutes before
battery shutdown.
Off Enables an audio alarm 5 minutes before
battery shutdown.