Compaq 3000 Series Power Supply User Manual


 
Configuration 4-7
4.
To toggle the selected configuration parameter value, press the
TEST/ALARM RESET button ( ). The UPS will acknowledge
compliance with a short beep.
NOTE: For nominal voltage configuration parameters 1, 2, 3, and 10—selecting an ON
value for any one parameter automatically sets the other three possibilities to OFF.
5.
To scroll through the configuration parameters, press the ON button
( ). The UPS acknowledges confirmation with a short beep. Monitor
the LED display (see Figure 4-2; LED 1 blinks to indicate that
parameter 1 is selected, LED 2 blinks when parameter 2 is selected, and
so on).
6.
Repeat Steps 2 through 5 as required. Continue until all changes have
been made.
7.
To exit the Configure mode at any time:
Press the ON ( ) and TEST/ALARM RESET buttons ( )
simultaneously, or
after parameter 15 is accessed, press the ON ( ) button.
The UPS will acknowledge compliance with a short beep.
Optimizing Battery Life
by Matching the Utility Voltage
Optimize UPS battery life by using the configuration parameters to select the
best nominal voltage range for the UPS installation.
When utility voltage is outside the selected operating range, the UPS supplies
battery power to the load segments. Maximize the UPS battery life by
configuring the UPS so that the utility voltage is normally within the selected
operating range.