Delta Electronics IFD9507 Network Card User Manual


 
Ethernet Communication Module IFD9507
DVP-PLC Application Manual
21
General
Status
Extended Status Explanation and Description
0x01 0x0114 VENDOR ID OR PRODUCT CODE MISMATCH
The Product Code or Vendor Id specified in the electronic key
logical segment does not match the Product Code or Vendor Id of in
the target device.
0x01 0x0115 PRODUCT TYPE MISMATCH
The Product Type specified in the electronic key logical segment
does not match the Product Type of in the target device.
0x01 0x0116 REVISION MISMATCH
The major and minor revision specified in the electronic key logical
segment does not correspond to a valid revision of the target
device.
0x01 0x0315 INVALID SEGMENT IN CONNECTION PATH
Invalid Segment Type or Segment Value in Connection Path This
extended status code is the result of a device being unable to
decode the connection path. This could be caused by an
unrecognized path type, a segment type occurring unexpectedly, or
a myriad of other problems in the connection path.
10 Setting up the Software - DCISoft
This section gives instructions on how to set up IFD9507 by DCISoft and explanations on each setup page.
IFD9507 is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the firewall.
See the explanations below on the software.
10.1 Setting up Communication & Searching for Modules in DCISoft
Broadcast search
1. Open DCISoft on the PC and click on the “IP Search” icon.
2. You will see the network modules found.