Eaton Electrical 9130 Power Supply User Manual


 
OPERATION
Eaton
®
9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com
39
Table 2 shows the basic menu structure.
Table 2. Menu Map for Display Functions
Main Menu Submenu Display Information or Menu Function
UPS Status Main status (mode and load) / Notice or Alarm status (if any) /
Battery status (state and charge level)
Event Log Displays up to 127 events and alarms
The Event Log is also available through the serial port. See
“Retrieving the Event Log” on page 47.
Measurements Load W VA / Load A pf / Output V Hz / Input V Hz / Bypass V Hz /
Input Line Events / Battery V min
Control
Go to Bypass Transfers the UPS system to internal Bypass mode
When this command is active, the option changes to “Go to
Normal.”
Start Battery Test Starts a manual battery test
See “Testing New Batteries” on page 72.
Reset Error State Clears a “Battery Test Failed” alarm
Load Segments Load segment 1: ON | OFF
Load segment 2: ON | OFF
These commands overrule user settings for load segments. See
“Configuring Load Segments” on page 49.
Restore Factory
Settings
Returns all settings to original values
Identification UPS Type / Part Number / Serial Number / Firmware
Settings
User Settings See Table 3 for details.
Service Settings This menu is password-protected.