Eaton Electrical 9130 Power Supply User Manual


 
SPECIFICATIONS
Eaton
®
9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com
87
Table 22. Environmental and Safety (All Models)
120 Vac Models 208/230/240 Vac Models
Surge Suppression ANSI C62.41 Category B3
(6 KV Ring and Combination)
EN 61000-2-2
EN 61000-4-2, Level 3
EN 61000-4-3, Level 2
EN 61000-4-4, Level 2 (also on signal ports)
EN 6100-4-5, Level 3 Criteria A
EN 61000-4-6, Level 2
EN 61000-4-8, Level 2
EN 6100-4-11
EMC Certifications <1500 VA: FCC Class B, VCCI Class B,
EN 55022 Class B
>
2000 VA: FCC Class A, VCCI Class A,
EN 55022 Class A
CE per IEC/EN 62040-2,
Emissions: Category C1,
Immunity: Category C2
EMC (Emissions) IEC 62040-2:ed2:2005 / EN 62040-2:2006
Safety Conformance UL 1778, IEC 62040-1-1, IEC 60950-1
Agency Markings CE, UL, CUL, NOM
Operating Temperature 0°C to 40°C (32°F to 104°F) in Online mode, with linear derating for altitude
NOTE Thermal protection switches load to Bypass in case of overheating.
Storage Temperature -20°C to 40°C (-4°F to 104°F) with batteries
-25°C to 55°C (-13°F to 131°F) without batteries
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity 5–90% noncondensing
Operating Altitude Up to 3,000 meters (9,843 ft) above sea level
Transit Altitude Up to 10,000 meters (32,808 ft) above sea level
Audible Noise <50 dBA at 1 meter typical
Leakage Current <1.5 mA