UPS Shutdown
To shut down the UPS:
1. Press the
button on the front panel for three seconds.
The UPS starts to beep and shows a status of “UPS off pending...”.
The UPS then transfers to Standby mode, and the
indicator
turns off.
NOTE Releasing the button before three seconds returns the UPS to its original
operating mode.
2. Switch off utility power where the UPS is connected.
Transferring the UPS Between Modes
From Normal to Bypass Mode. Press any button to activate the menu
options, then select CONTROL and GO TO BYPASS.
From Bypass to Normal Mode. Press any button to activate the menu
options, then select CONTROL and GO TO NORMAL.
Retrieving the Event Log
To retrieve the Event Log through the display:
1. Press any button to activate the menu options, then select
EVENT LOG.
2. Scroll through the listed events.
To retrieve the Event Log through the serial port:
1. From the communication device connected to the serial port, send
one of the following command sequences: ESC-L (ASCII characters
27 and 76) or ESC-I (ASCII characters 27 and 108).
The UPS returns a header containing the UPS identification (UPS
type, part number, and serial number), firmware version, and the
current date and time, followed by the event history.
2. Use the connected communication device to view or print the
information. The report is delivered in ASCII format.