Emerson 225-600KVA Power Supply User Manual


 
Installation Drawings
17 Liebert
®
NX
Figure 13 Front Terminal detail drawing
GROUND BUS DETAIL
BUS TERMINATION DETAIL
FOR POS. AND NEG. BUSBAR
NOTES:
1. All dimensions are in in [mm].
2. Top and bottom cable entry available through removable access plates.
3. Control wiring and power wiring must be run in separate conduit.
4. Aluminum and copper-clad aluminum cables are not recommended.
5. All wiring is to be in accordance with national and local electrical codes.
6. For cabinets ordered as stand-alone, the negative and positive terminal
bus does not extend to full width of battery cabinet.
7. 24" minimum clearance above unit is required for air exhaust and service.
Negative Term. Bus (-)
Positive Term. Bus (+)
See Bus Termination
Detail
FRONT
TOP VIEW
FRONT VIEW
* Doors and covers removed for clarity
RIGHT SIDE VIEW
Ground Bus
(See Detail)
(SECTION "B")
(SECTION "B")
1.75
[44]
1.75
[44]
.56
[14]
TYP.
1.75
[45]
TYP.
1.75
[44]
Ø.56 X .75" SLOT
[Ø14 X 19]
TYP.
(+) (-)