Emerson 225-600KVA Power Supply User Manual


 
Installation Drawings
Liebert
®
NX
18
Figure 14 Liebert NX Stand-Alone Junction Cabinet terminal wiring
Notes:
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduit.
3. Aluminum and copper-clad aluminum cables are not recommended.
4. Widths are without side panels. The width is 32.1" (815mm) with side panels.
5.The depth dimension includes the front door and rear panel.
13.7
(348)
Negative BusGround Bus Positive Bus
Ground
Bus
Negative
Bus
Positive
Bus
9.0
(228)
8.7
(221)
7.4
(189)
.56
(14) Typ
.56
(14) Typ
.56 (14)
Typ
13.6
(346)
Front View
Right Side
View
41.3
(1050)
76.9
(1952)
30.9 (785)
33.5 (805)
2.2 (55)
16 Places
2.2 (55)
18 Places
2.2 (55)
18 Places
2.2 (55)
16 Places
1.7 (44) X 0.7 (18)
Slot 16 Places
Typ. Each Busbar
1.8 (45)
16 Places
2.2 (55)
18 Places
Do not double stack lugs
(two lugs on same side of
busbar). This is to prevent
the cables from coming into
contact with other busbars.
DUAL LUG
CONNECTION DETAIL
Lugs
Busbar
Bolt
CB1-3
CB1-3