Installation Drawings
21 Liebert
®
NX
Figure 17 Attached battery cabinet connections
Figure 18 Ground strap location for connected cabinets
Jumper Busbars
(supplied with battery cabinet)
Jumper Busbars
(supplied with battery cabinet)
Note: Torque to 240in-lb (27 N-M)
Note: Connections cannot be made
if cabinets ordered as stand-alone.
REFERENCE OF
CORNER POST OF
CONNECTED CABINETS
CABINET-TO-CABINE T
BOLTING INSTRUCTIONS
NOTES:
1. Apply ground strap hardware to specified locations.
2. Torque Values: M6: ( 5 Nm ) 40 IN-LB
M10: ( 14 Nm ) 120 IN-LB
FRONT SIDE OF
UNITS
BATTERY
CABINET
TYPICAL GROUND STRA P INSTALLATION
FOR BATTERY CABINET TO
UPS OR ANCILLARY CABINET CONNECTIONS
2
2
FRONT SIDE OF
UNITS
TYPICAL GROUND STRA P INSTALLATION
FOR BATTERY CABINET TO BATTERY CABINET
CONNECTIONS
BATTERY
CABINET
BATTERY
CABINET
1
1
A
B
DETAIL A
DETAIL B