Emerson 40-200KVA Power Supply User Manual


 
Specifications and Technical Data
112
13.3 Cable size and tightening torques
Table 38 External cabinet dimensions, including side panels
Wide Parallel Cabinet
Unit Width Depth Height
mm (inch) 1240 (48.8) 965 (38) 2000 (78.7)
Narrow Parallel Cabinet
Unit Width Depth Height
mm (inch) 845 (33.2) 965 (38) 2000 (78.7)
33 in. Battery Cabinet
Unit Width Depth Height
mm (inch) 845 (33.2) 965 (38) 2000 (78.7)
Table 39 Cable size tightening torque at Liebert
®
NX
40kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
410 N-m
Main Input
(Dual Input)
410 N-m
Bypass Input
(Dual Input)
410 N-m
Output 3 10 N-m
Table 40 Cable size tightening torque at Liebert NX 60kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
110 N-m
Main Input
(Dual Input)
110 N-m
Bypass Input
(Dual Input)
210 N-m
Output 2 10 N-m
Table 41 Cable size tightening torque at Liebert NX 80kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
2/0 10 N-m
Main Input
(Dual Input)
2/0 10 N-m
Bypass Input
(Dual Input)
1/0 10 N-m
Output 1/0 10 N-m