Emerson 40-200KVA Power Supply User Manual


 
Operator Control and Display Panel
87
System
Sout (kVA) Sout: Apparent power
Pout (kW) Pout: Active power
Qout (kVAR) Qout: Reactive power
Single unit, no parallel data When configured as a single unit, UPS has only native load, no system load.
Battery
Battery voltage (V) Battery bus voltage
Battery current (A) Battery bus current
Battery temperature (°C) Internal battery temperature °C
Remain Time Min. Battery run time remaining.
Battery boost charging Battery is boost charging.
Battery float charging Battery is float charging.
Battery disconnected Battery is not connected.
Records (History Log) Displays all records in the history log.
Language (choices for text displayed) User may select any of 12 languages for LCD text.
Settings
Settings
Display contrast Adjust the LCD contrast
Date format set Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D
Date & time Set the date and time
Comm1 baud rate Communication baud rate setting for Liebert IntelliSlot 1
Comm2 baud rate Communication baud rate setting for Liebert IntelliSlot 2
Comm3 baud rate Communication baud rate setting for Liebert IntelliSlot 3
Communication address This setting is applicable to RS485 communication mode.
Communication mode Communication Mode Setting
Callback times
When Liebert IntelliSlot 1 Communication mode is Modem, this parameter
sets the number of times a number is redialed to send an alarm notification.
Phone No.1
When Liebert IntelliSlot 1 Communication mode is Modem, this is the first
phone number to be dialed (to send an alarm notification).
Phone No.2
When Liebert IntelliSlot 1 Communication mode is Modem, this is the second
phone number to be dialed (to send an alarm notification).
Phone No.3
When Liebert IntelliSlot 1 Communication mode is Modem, this is the third
phone number to be dialed (to send an alarm notification).
Command password User can modify the command password.
Audible Alarm User can Enable and Disable the UPS audible alarm.
Command
(start/stop
battery &
system
tests)
Battery maintenance test
This test performs a partial discharge of the battery to obtain a rough estimate
of the battery capacity. Load must be between 20% and 80%.
Battery capacity test
This test performs a full discharge of the battery to obtain a precise measure of
the battery capacity. Load must be between 20% and 80%.
System test
This is a self-test of the UPS. When the user activates this function, a pop-up
window appears about 5 seconds later to show the results.
Stop testing
Manually stops a battery maintenance test, battery capacity test or system
test.
Freshening Charge
Allows a temporary Equalize charge for the batteries. This charge is
configurable for 1 to 36 hours.
Stop Freshening Charge Manually stops a Freshening Charge.
Modem Auto-answer
enable
Manually enable the modem’s auto-answer function.
Battery Commission Resets the UPS battery detection logic after new/fresh batteries are installed.
Version
UPS version
Provides UPS firmware version numbers for the inverter, rectifier and software
display board.
UPS model Provides UPS model information—for example, 480V-60Hz.
Table 31 Descriptions of UPS menus and data window items (continued)
Menu Type Item Type Explanation