Emerson 40-200KVA Power Supply User Manual


 
UPS Status Messages
117
APPENDIX A-UPS STATUS MESSAGES
Table 49 shows all event messages as they appear in the current status area of the LCD and in the
history log, along with a description and recommended actions, if any. For further information on the
current status area and the history log, see 2.11 UPS Status Messages.
Table 49 UPS status messages
Event Message Description / Suggested Action (if any)
Inverter Comm. Fail
The RS-485 communication between internal monitor and inverter has failed. Contact Liebert
Services at 800-543-2378 for assistance.
Rectifier Comm. Fail
The RS-485 communication between internal monitor and rectifier fails. Contact Liebert
Services at 800-543-2378 for assistance.
Parallel Comm. Fail
The CAN communication between different UPS units within a parallel system has failed.
Check if there are some UPS units not powered on in the parallel system. If so, power on these
UPS units and check if the alarm disappears.
Press Fault Clear push button.
If alarm does not clear, contact Liebert Services at 800-543-2378
Battery Overtemp. The battery temperature is over limit. Check the battery temperature and ventilation
Replace Battery Battery should be replaced. Contact Liebert Services at 800-543-2378 for assistance.
Battery Low Pre-warning
Before the end of discharging, battery under-voltage pre-warning should occur. After this pre-
warning, battery should have the capacity for 3 minutes discharging with full load. The time is
user configured from 3 to 60 minutes.
Shut down the load in time to prevent damage to equipment and data.
Battery End of Discharge
Inverter turned off due to low battery voltage.
Check the utility failure and try to recover it.
Mains Volt. Abnormal
Mains voltage exceeds the upper or lower limit and results in rectifier shutdown.
Check the input line-to-line voltage amplitude of rectifier.
Mains Undervoltage
Mains voltage is undervoltage 288V~384V line to line voltage with derated load.
Check the input line-to-line voltage amplitude of rectifier.
Mains Freq. Abnormal
Mains frequency is out of limit range and results in rectifier shutdown.
Check the rectifier’s input voltage frequency
Rectifier Fault Contact Liebert Services at 800-543-2378 for assistance.
Input Inductor Overtemp.
The temperature of rectifier inductor of rectifier common mode inductor is too high to keep the
rectifier running.
Check the ambient temperature and ventilation; contact Liebert Services at 800-543-2378 for
assistance.
Rectifier Overtemp.
The temperature of the heat sink is too high to keep the rectifier running.
The UPS can recover automatically. Check the environment and ventilation.
Charger Fault The charger has a fault. Contact Liebert Services at 800-543-2378 for assistance.
Control Power 1 Fail
Control Power 1 has failed or has been lost. Contact Liebert Services at 800-543-2378 for
assistance.
Mains Phase Reversed Input phase sequence is inverse. Contact Liebert Services at 800-543-2378 for assistance.
Rectifier Overcurrent The current of rectifier is over limit. Contact Liebert Services at 800-543-2378 for assistance.
Soft Start Fail
Rectifier could not start due to low DC bus voltage. Contact Liebert Services at 800-543-2378
for assistance.
Bypass Unable to Trace
This alarm is triggered by an inverter software routine when the amplitude or frequency of
bypass voltage is beyond the normal range.
The amplitude threshold is fixed for positive and negative 10% rating.
This alarm automatically resets once the bypass voltage goes normal.
First verify that the bypass voltage and frequency displayed on the panel is within the selected
range. Note here the rated voltage and frequency are specified by “Output voltage level” and
“Output frequency level” respectively.
If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency
presented to the UPS. Check the external supply if it is found to be faulty.
Contact Liebert Services at 800-543-2378 for assistance.