Emerson 480V Power Supply User Manual


 
UPS Specifications
33
5.0 UPS SPECIFICATIONS
These specifications describe requirements for the Liebert NX UPS.
5.1 Conformity and Standards
The UPS has been designed to conform to the following standards:
IEC 61000-4-5
•ASME
CSA 22.2, No. 107.1
FCC Part 15, Class A
ISO 9001
National Electrical Code (NFPA-70)
NEMA PE-1
•OSHA
UL Standard 1778
The UPS system has UL and c-UL approval.
5.2 UPS Environmental
The UPS is designed to operate under the following environmental conditions without damage or deg-
radation in electrical operating characteristics:
5.3 UPS Mechanical Characteristics
Table 6 Environmental characteristics
Rated Power
40kVA 60/80kVA 100/120kVA 160/200kVA
Operating Temperature, UPS 32°F to 104°F (0°C to 40°C)
Optimal Operating Temperature, Battery 68°F to 86°F (20°C to 30°C)
Relative Humidity 0 to 95%, non-condensing
Acoustical Noise, dBA at 39 in. (1m)
(Fans at Low Speed)
61 61 63 68.5
Altitude of Operation 1000m per IEC 62040/3
Storage-Transport Temperature, UPS, -4°F to 158°F (-20°C to 70°C)
Storage-Transport Temperature, Battery -4°F to 86°F (-20°C to 30°C)
Table 7 UPS mechanical characteristics
Parameter 40/60/80kVA 100/120kVA 160/200kVA
Width, in. (mm) 23.6 (600) 48.8 (1239)
Depth, in. (mm) 38 (965) 38.5 (979)
Height, in. (mm) 78.5 (2000) 78.5 (2000)
Heat Dissipation, BTU/H (kWH) 20,273 (5.9) 28,196 (8.3) 46,400 (13.6)
Airflow, CFM (m
3
/h) 1760 (2990) 1668 (2834)
Cable Entry Bottom or Top
Color Black (Z-0350)
Protection Grade (with open/closed front doors) IP 20
Weight, lb (kg) 1180 (535) 1290 (585) 2201 (1000)