Operation
20
3.0 OPERATION
3.1 Display Screen and Operator Controls
Each Liebert Series 610 UPS cabinet is equipped with a microprocessor-based Operator Control Panel
and Display Screen and System Control Panel designed for convenient and reliable operation. The
System Control Cabinet (SCC) performs different functions than the UPS modules. Each cabinet has
the controls and displays required to operate and monitor its functions. The locations of operator con-
trols are shown in Figure 8 through Figure 11.
The front location of the control panel enables the user to quickly identify the current status of the
UPS system and to perform most of the manual operations. The operator display screen is driven by
an easy-to-follow menu-prompted software program.
Features
The Liebert Series 610 interface display system enables the operator to easily perform the following:
• Obtain a quick indication of operational status:
• Is the critical bus OK?
• Is the UPS system OK?
• Which UPS modules are available?
• Is the battery available?
• Is the bypass line available?
• Monitor the power flow through the UPS system and monitor all meter readings:
• Is the critical load being supplied power from the UPS system or bypass?
• Are input, battery and output voltage, frequency and current readings at nominal levels?
• How much battery time is still available during an outage?
• Is the battery recharging after discharge?
• Execute operational procedures:
• Perform critical bus transfer/retransfer between the UPS system and the bypass line.
• Start up and shut down the UPS system and each module.
• Shut down the system and all modules instantly in the event of an emergency.
• Access status reports and history files:
• Obtain a complete listing of the present status of the UPS system and all modules (input, out-
put and battery voltage, frequency and current readings and any alarms that may be
present).
• Review a complete history report of all events leading up to and immediately after a fault con-
dition.
• Examine an archive listing of all alarm conditions that have occurred over a period of time.
• Make adjustments to programmable parameters (access limited by Security Access function):
• Set the date and the time functions.
• Change the auto-dial phone number and the modem options.
• Select the number of auto-retransfer attempts.
• Make adjustment to the UPS output voltage before performing a manual load transfer.