Falcon XG3K-1T Power Supply User Manual


 
19
CAUTION: When the UPS output voltage is set to 100Vac, the maximum amount of load that
can be connected to the UPS must be derated (reduced). See the Specifications at the end of
this manual for the derating information on your model.
Output Voltage Function BIT(s) Status Bit (BIT 7)
120Vac BIT 0 & BIT 1 BIT 0 Enabled (dot), BIT 1 Enabled (dot)
115Vac BIT 0 & BIT 1 BIT 0 Disabled (no dot, BIT 1 Enabled (dot)
110Vac BIT 0 & BIT 1 BIT 0 Enabled (dot, BIT 1 Disabled (no dot)
100Vac BIT 0 & BIT 1
BIT 0 Disabled (no dot, BIT 1 Disabled (no dot)
An Example of How to Set the UPS Output Voltage to 115Vac
1. Press the “FUNTION/TEST” and “SET/ALARM SILENCE”
buttons at same time and hold them for one second. The unit will
emit one alarm beep and then enter the setup CONFIGURATION
MODE.
2. Press the “FUNCTION/TEST” button repeatedly and move the dot to
function BIT 0.
3. Press the “SET/ALARM SLIENCE” button once or twice to Disable
(no dot) Status BIT 7.
4. Press the “FUNCTION/TEST” button repeatedly and move the dot to
function BIT 1.
5. Press the “SET/ALARM SLIENCE” button once or twice to Enable
(dot) Status BIT 7.
6. Press the “SET/ALARM SLIENCE” and “FUNCTION/TEST” buttons
at same time again and hold for one second. The alarm buzzer will
sound one short beep to acknowledge the UPS has stored the
settings.
7. You must now restart the UPS to affect the new voltage setting.
7.0 COMMUNICATIONS
All XG Series UPSs are provided with the following communication ports:
RS-232 port with standard DB-9F serial port connector.
An advanced communications option slot is provided on the rear panel of the UPS.
Unless an advanced communications option has been previously purchased and
installed, the port will be covered with a small cover plate. This plate will be secured
with screws.
CAUTION: NEVER INSTALL OPTION CARDS THAT HAVE NOT BEEN
SUPPLIED BY FALCON ELECTRIC AS UPS DAMAGE MAY
RESULT.
Advanced communications option cards available from Falcon are:
Internal SNMP/HTTP Agent Board
Standard Dry Contact Interface Board (Novell style)
Dry Contact Interface Board with On-Bypass Signal
Standard Optically-Isolated Contact Interface Board
APC Style Dry Contact Interface Board