6
BATTERY
The XG Series UPS utilizes a flame retardant battery pack comprised of four 12V 7 AH, valve-
regulated, and sealed lead acid batteries. All XG battery packs are interchangeable. They are
easy to install or change. To maintain battery design life, the user should operate the UPS in
an ambient temperature of 68
o
F to 77
o
F (20
o
C to 25
o
C). Extended Battery modules are available
to provide extend battery run times.
CHARGER
The battery charger uses the energy from the utility power to continuously charge the UPS
batteries. The charger operates in “constant power” mode. The UPS batteries are being
charged whenever the UPS is plugged in. The charger will continue to operate as long as the
utility voltage is over 60 Vac.
BYPASS TRANSFER SWITCH
The XG Series UPS automatically switches to bypass to energize the connected load when
UPS encounters an overload, over temperature, over input current, over crest-factor load
(designed for 3:1 nonlinear load), or a UPS failure condition. Should any of these events
occur, the UPS will automatically transfer to bypass mode with an audible alarm, and provide
a “bypass” indication on the LCD display.
OUTPUT FILTER
This filter prevents electro-magnetic conductance (EMC) leakage and RFI noise to the UPS
output.
3. 0 INSTALLATION
UNPACKING
The XG Series UPS may be shipped in a number of boxes, depending on the model and
configuration ordered. The number of boxes you have received should be as indicated:
MODEL BATTERY MODULE NUMBER OF BOXES
XG1.5K-1T n/a (internal battery pack) 1 box shipped
XG2.2K-1T 1 battery module 2 boxes shipped
XG3K-1T 1 battery module 2 boxes shipped
If you have not received the proper number of boxes, please contact Falcon Electric Customer
Service at 1-800-842-6940
This UPS is shipped complete with all cables required for operation, along with UPSILON
software, and rackmount ears for 19” shelf mounting. A full list of the box contents is
provided as follows: