FieldServer FS-8700-47 Computer Drive User Manual


 
FS-8700-47 DNP 3.0 Driver Manual Page 32 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Appendix A.8. DNP_Stats
In addition to the standard FieldServer communication statistics described in the FieldServer
Configuration Manual the DNP 3.0 Driver can expose some driver statistics by writing to a data array
called “DNP_STATS”
The following example shows how this special Map Descriptor can be configured. Only one of these
Map Descriptors may be specified per FieldServer.
Nodes
Node_Name ,Protocol ,Node_ID
Null_Node ,DNP ,100
Data_Arrays
Data_Array_Name ,Data_Format ,Data_Array_Length
DNP_STATS ,UINT32 ,100
Map_Descriptors,
Map_Descriptor_Name ,Data_Array_Name, ,Node_Name
dnp-stats ,DNP_STATS, ,Null_Node
The driver stores the following data in the data array EGD_STATS.
Array
Element
Contents
1 DRV_DLL_CLIENT_SENDS_MSG
2 DRV_DLL_CLIENT_SENDS_BYTES
3 DRV_DLL_SERVER_SENDS_MSG
4 DRV_DLL_SERVER_SENDS_BYTES
5 DRV_DLL_CLIENT_RCVS_MSG
6 DRV_DLL_CLIENT_RCVS_BYTES
7 DRV_DLL_SERVER_RCVS_MSG
8 DRV_DLL_SERVER_RCVS_BYTES
9 DNP_UPD_TMO
10 DNP_UPD_PROTO
11 DNP_UPD_NOISE
12 DNP_UPD_CHECK
12 DNP_UPD_STATION
14 DNP_UPD_LENGTH
15 DNP_UPD_EXCEPT
16 DNP_UPD_STREAMING
17 DNP_UPD_FUNCTION
18 DNP_UPD_PREMATURE
19 DNP_UPD_IC_TIMEOUT
20 DNP_UPD_NAK
21 DNP_UPD_OVERRUN
22 DNP_UPD_HOLD_TIMEOUTS
23 DNP_UPD_NODE_OFFLINE
24 DNP_UPD_NO_SLAVE
25 DNP_UPD_NO_START
26 DNP_UPD_SCADA_BYTES_RECD
27 DNP_UPD_SCADA_BYTES_SENT
28 DNP_UPD_SCADA_MSG_SENT
29 DNP_UPD_SCADA_MSG_RECD